Thermocouple Cable



Benefits :

  • Generates measurable electrical energy with dissimilar conductors
  • Enhanced performance in high operating temperature environments
  • Color coded insulation and jacket materials for easy identification


Features :

  • Meets ANSI/IEC Type E/J/K/T/EX/JX/KX/TX standards
  • Multiple alloy options for measuring electrical readings
  • Additional constructions available upon request


Details :

  • Limits of error per ANSI MC96.1-1982. Limits shown do not include system or installation error. Percentages refer to the temperature being measured.
  • The Temperature Range and Limits of Error are for standard grade thermocouples. Reference ANSI MC96.1-1982 for special grade thermocouples.
  • The Temperature Ranges for type E, J, K and T thermocouple wires listed above pertain to 20 AWG wire.
  • ANSI = American National Standards Institute
  • Additional constructions available upon request.

Specifications

Conductor Material Copper
Packaging As per client requirement
Use in Thermocouple


Technical Data

ANSI Symbol Temperature Range (oC) (conductor only) Limits of Error Standard (oC) Jacket Color Insulation Color Code Conductor Identification
Positive
( + )
Negative
( - )
Positive
( + )
Negative
( - )
E 0 to 340
340 to 540
±1.7oC
±0.50%
Brown Purple Red Chromel®
Non-magnetic
Constantan
Silver Color
J 0 to 293
293 to 480
±2.2oC
±0.75%
Brown White Red Iron
Magnetic
Constantan
Non-magnetic
K 0 to 340
340 to 540
±1.7oC
±0.50%
Brown Yellow Red Chromel®
Non-magnetic
Alumel®
Magnetic
T 0 to 340
340 to 540
±1.7oC
±0.50%
Brown Blue Red Copper
Copper Color
Constantan
Non-magnetic
EX 0 to 200 ±1.7oC Purple Purple Red Chromel® Constantan
JX 0 to 200 ±2.2oC Black White Red Iron Constantan
KX 0 to 200 ±2.2oC Yellow Yellow Red Chromel® Alumel®
TX 0 to 200 ±1.0oC Blue Blue Red Copper Constantan
Thermocouple Identification and Limits of Error – Reference Junction 0°C *