Omron Sensor


Omron Sensor

Specifications

Use In Electrical Instruments
Min. Order Quantity 100 Piece
Packaging As per client requirement

Provides two types of Masters, a Master Unit with screw-less clamp terminal blocks and a Master Unit for M12 Smartclick connectors, as IO-Link compliant devices and Sensors for connecting to the screw-less clamp terminals or to the M12 connector terminals that support each Master.

Details :

  • Downtime can be reduced.
  • Notifies you of faulty parts and such phenomena in the Sensor in real time.
  • The frequency of sudden failure can be decreased.
  • Notifies you of objects being too far or too close.
  • The efficiency of changeover can be improved.
  • The batch check for individual sensor IDs significantly decreases commissioning time.
  • Standard Sensor for detecting ferrous metals.

Yes! I am interested

Submit Your Requirement


Specification

Item Size M12 M18 M30
Shielded Shielded
Model E2E-X3B4-IL[] E2E-X7B4-IL[] E2E-X10B4-IL[]
Sensing distance 3 mm ±10% 7 mm ±10% 10 mm ±10%
Set distance *1 0 to 2.4 mm 0 to 5.6 mm 0 to 8 mm
Differential travel 10% max. of sensing distance
Detectable object Ferrous metal
(The sensing distance decreases with non-ferrous metal. Refer to Engineering
Data on Catalog.)
Standard sensing object Iron, 12 × 12 × 1 mm Iron, 18 × 18 × 1 mm Iron, 30 × 30 × 1 mm
Response frequency *2 1 kHz 0.5 kHz 0.4 kHz
Power supply voltage 10 to 30 VDC (including 10% ripple (p-p))
Current consumption 20 mA max.
Control output Load current 100 mA max.
Residual voltage 2 V max. (Load current: 100 mA, Cable length: 2 m)
Indicators *1 In the Standard I/O mode (SIO mode): Operation indicator (orange, lit) and stability
indicator (green, lit)
In the IO-Link mode: Operation indicator (orange, lit) and communication indicator
(green, blinking at 1 s intervals)
Operation mode PNP NO/NC switching type (Factory setting: NO)
Refer to the timing charts under I/O Circuit Diagrams on Catalog for details.
Protection circuits Power supply reverse polarity protection, output reverse polarity protection, surge
suppressor, and output short-circuit protection
Ambient temperature range Operating/Storage: -25 to 70°C (with no icing or condensation)
Ambient humidity range Operating/Storage: 35% to 95% (with no condensation)
Temperature influence ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C
Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
directions
Shock resistance Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions
Degree of protection IEC 60529 IP67, in-house standards: oil-resistant *3
Connection method Pre-wired Models (Standard cable length: 2 m), Pre-wired Connector Models
(Standard cable length: 0.3 m)
Materials Case Nickel-plated brass
Sensing surface PBT
Clamping nuts Nickel-plated brass
Toothed washer Zinc-plated iron
Main IO-Link functions Operation mode switching between NO and NC, self diagnosis enabling, excessive
proximity judgment distance selecting, timer function of the control output and
timer time selecting, instability output (IO-Link mode) ON delay timer time selecting
function, monitor output, operating hours read-out, and initial reset
Communication
specifications
IO-Link
specification
Ver 1.1
Baud rate -IL3: COM3 (230.4 kbps), -IL2: COM2 (38.4 kbps)
Data length PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2)
Minimum cycle
time
-IL3 (COM3): 1 ms, -IL2 (COM2): 2.3 ms
Accessories Instruction manual